EVALUATION OF DOMINO EFFECT CAUSED BY POOL FIRE IN A TANK FARM
Keywords:
Major Hazard Installation, Storage Tank, Pool Fire, Thermal Radiation, Dominio EffectAbstract
Major hazard installations (MHIs) such as oil refineries, petrochemical plants and terminals use large capacity storage tanks for storing crude oil and by-products. Pool fire is one of the most common types of storage tank fire incidents. This technical article aims to investigate the domino effect from a pool fire in a tank farm consist of eight large floating roof storage tanks. Four storage tanks have been studied. A crude oil storage tank was selected as the primary tank (source tank). Point source and plume solid models were used for the estimation of the thermal radiation. It has been noted that the thermal radiation from the source tank to the adjacent tank in the same dike exceeds the threshold heat radiation level and might resulted in domino effect however the thermal radiation from the source tank alone does not reach the threshold level for the tanks in the other dike. Also, it has been found that the thermal radiation from both the primary and secondary tanks just reach the threshold level for the farther away tank in the other dick. The domino effect occurs provided that the firefighting system is not activated and the emergency response team does not intervene within ten minutes.